F-gas Regulation (EU) 2024/573: fluorinated greenhouse gases in cooling and fire equipment

Requires operators of cooling, air-conditioning, heat pump, fire protection and switchgear equipment above set gas charges to check for leaks, fit leak detection above higher charges, keep records per machine and use certified technicians.

  • 5requirementsin our own words
  • 1edition Regulation (EU) 2024/573
  • 27places where it is a duty of 30 assessed
  • 18 Oct 2026last checkedat the sources below

Where it applies

It is a duty in 27 of 30 places, and 3 need a closer read. The outcome holds under the conditions shown and says nothing about any one site.

WhereOutcomeBasisConditionsAuthority and route
All 27 EU Member StatesAppliesRequired by law In forceEquipment: stationary refrigeration, air-conditioning, heat pump, fire protection, organic Rankine cycle and electrical switchgear equipment; leak checks at 5 tonnes CO2-equivalent or more of fluorinated gas (or 1 kg of the Annex II gases); leakage detection systems at 500 tonnes CO2-equivalent or more (100 kg of Annex II gases) for refrigeration, air-conditioning, heat pump and fire protection equipmentExempt: hermetically sealed equipment labelled as such under 10 tonnes CO2-equivalent; certain switchgear Direct EU regulation; national authority enforces and runs technician certification.Not stated
SwitzerlandNeeds reviewRequired by law Status not confirmedNone stated Switzerland regulates fluorinated gases in its own chemicals-risk ordinance; not read in this pass.Not stated
United KingdomNeeds reviewRequired by law Status not confirmedNone stated Great Britain has its own Fluorinated Greenhouse Gases Regulations 2015; thresholds not read here.Not stated
NorwayNeeds reviewRequired by law Status not confirmedNone stated EEA relevance; Norwegian implementation not checked.Not stated

What it asks for

5 requirements, each in our own words with the evidence an assessor would expect and who on a site usually owns it. Read the clause itself on the scheme owner's page.

RequirementEvidence expectedOwnerWhen
Inventory every machine with fluorinated gas: gas type, charge and equivalent tonnes of CO2. Equipment register Record, checked by document reviewM&E lead Every year Record keeping, one site
Check for leaks at the frequency set by charge size. Leak check reports Test report, checked by document reviewM&E lead Every year Inspection, one site
Fit leakage detection above the higher charge threshold. Detection system records Record, checked by document reviewM&E lead Continuous Technical limit, one site
Keep records per machine: gas added, recovered, service dates. Per-machine log Record, checked by document reviewM&E lead Continuous Record keeping, one site
Use certified technicians for installation, service and recovery. Technician certificates Certificate, checked by document reviewProcurement On each change Authorisation, the organisation

Editions

Which text is in force, from when, and which one it replaced.

EditionStatusPublishedIn effectReplaces
Regulation (EU) 2024/573 Current 20 Feb 2024Not stated None named

About the programme

Assessed by
A regulator or authority
Scope
piece of equipment (chiller, air-conditioning unit, fire-protection system, switchgear)
Levels
thresholds by tonnes CO2-equivalent charge
Validity
Check frequency depends on charge size.
Accreditation route
Certified personnel and companies under Art. 10
Regulator
National F-gas competent authorities
Official body
European Parliament and Council
Who asks for it
Regulator, Insurer
Where it is used
EU27 directly; GB has its own F-gas regulations