EN 50600 data centre facilities and infrastructures series

A multi-part European series on how to plan, build and operate data centre buildings, power, cooling, cabling and security, plus the key performance indicator methods (such as PUE, renewable share, energy reuse, water use) that EU and German law now cite.

  • 6requirementsin our own words
  • 4editions DIN EN 50600-4-7, August 2020
  • 0places where it is a duty of 30 assessed
  • 18 Oct 2026last checkedat the sources below

Where it applies

It is voluntary in the 30 places assessed. The outcome holds under the conditions shown and says nothing about any one site.

WhereOutcomeBasisConditionsAuthority and route
All 30 placesAppliesVoluntary In forceNone stated No law in this country requires it; customers, lenders or tenders decide.Not stated

What it asks for

6 requirements, each in our own words with the evidence an assessor would expect and who on a site usually owns it. Read the clause itself on the scheme owner's page.

RequirementEvidence expectedOwnerWhen
Plan the building, power, cooling, cabling and security of a data centre to a chosen class from the series. Design basis document stating the target classes and the series parts used Drawing, checked by document reviewM&E lead Once Governance, one site
Choose the redundancy of power distribution to match the availability class. Single-line diagrams and redundancy analysis Drawing, checked by document reviewM&E lead On each change Technical limit, one site
Choose the redundancy of cooling and its failure behaviour to match the class. Cooling schematics and failure-mode analysis Drawing, checked by document reviewM&E lead On each change Technical limit, one site
Zone the site by protection class and control entry to each zone. Zoning plan and access-control records Record, checked by document reviewSecurity lead Continuous Technical limit, one site
Measure efficiency indicators (energy, renewable share, heat reuse, water) with the series' stated methods, as EU and German law cite them. Metering concept and KPI calculations Meter data, checked by document reviewM&E lead Every year Disclosure, one site
Document operation and maintenance management in line with the series' operations part. Operations manual and maintenance schedules Policy, checked by document reviewSite manager Continuous Governance, one site

Editions

Which text is in force, from when, and which one it replaced.

EditionStatusPublishedIn effectReplaces
DIN EN 50600-4-7, August 2020 Part 4-7 (edition cited in EnEfG Anlage 3)Current Edition as cited by German law; may have newer editions.Not statedNot stated None named
DIN EN 50600-4-6, November 2020 Part 4-6 (edition cited in EnEfG Anlage 3)Current Edition as cited by German law; may have newer editions.Not statedNot stated None named
DIN EN 50600-4-3, November 2020 Part 4-3 (edition cited in EnEfG Anlage 3)Current Edition as cited by German law; may have newer editions.Not statedNot stated None named
DIN EN 50600-4-2, August 2019 Part 4-2 (edition cited in EnEfG Anlage 3)Current Edition as cited by German law; may have newer editions.Not statedNot stated None named

About the programme

Assessed by
Not specified
Scope
site
Levels
availability, protection and energy-efficiency classes (per series structure)
Validity
No scheme-wide certificate cycle found on an official page; conformity claims depend on the assessor chosen.
Accreditation route
not stated by the series owner on a reachable page
Who asks for it
Regulator, Public tenders, Enterprise and colocation customers
Where it is used
EU (cited by Delegated Regulation 2024/1364 and German EnEfG); series also used outside the EU